Usually the other side decides the protocol, so first check what the equipment or system you connect to supports. If you do have a choice, use these guidelines.

Situation Product
Connect semiconductor or display equipment to a factory host (MES). SECS/GEM
Read and write registers of PLCs, drives, meters, and sensors. Modbus
Integrate equipment from several vendors with SCADA or MES through information models and secure connections. OPC UA
Send measurements through a broker to many subscribers. OPC UA PubSub with MQTT
Test RS-232 or RS-485 communication without serial devices. Virtual serial ports

Equipment and hosts exchange messages defined by SEMI standards:

  • SECS-II (SEMI E5) defines message structure and data formats. A stream and function number identify each message, such as S1F13.
  • HSMS (SEMI E37) carries SECS-II messages over TCP/IP.
  • SECS-I (SEMI E4) carries SECS-II messages over an RS-232 serial line, mostly on older equipment.
  • GEM (SEMI E30) defines common equipment behavior: establishing communication, control state, variables, reports and events, alarms, remote commands, and recipes.

For GEM300, PDComm provides a declarative capability catalog that records, profile by profile, the GEM300 capabilities of an equipment configuration.

Modbus is a simple request-response protocol in which a client reads and writes four data tables of a server by address: coils, discrete inputs, input registers, and holding registers.

  • Modbus TCP runs over Ethernet, on port 502 by default.
  • Modbus RTU and ASCII run over RS-485 or RS-232 serial lines. One RS-485 bus connects several devices, told apart by their addresses.
  • Modbus/TCP Security protects Modbus TCP with TLS and restricts access by roles in certificates. Its default port is 802.
  • A gateway forwards TCP requests to devices on a serial bus.

OPC UA (IEC 62541) lets equipment and systems publish data, methods, and events as nodes in an address space.

  • Clients browse, read, and write nodes, and receive notifications through subscriptions when values change.
  • Certificate-based secure channels sign and encrypt the traffic.
  • With PubSub, a publisher sends data sets to many subscribers over UDP or through an MQTT broker.
  • The default port is 4840.

MQTT (OASIS MQTT 3.1.1 and 5.0) is a lightweight protocol in which publishers and subscribers exchange messages on topics through a central broker. PDComm provides MQTT as the broker transport of OPC UA PubSub: the OPC UA simulator publishes and subscribes to UADP messages through an MQTT 5.0 broker.